无功补偿技术对低压电网功率因数的影响

                         ——无功补偿技术对低压电网功率因数的影响

作者: 时间:2008-06-02 来源:互联网   字体颜色   阅读:0 次   评论:0

摘要:依据用电设备的功率因数,可测算输电线路的电能损失。通过现场技术改造,可使低于标准要求的功率因数达标,实现节电目的。本文分析了无功补偿的作用和补偿容量的选择方法,着重论述了低压电网和异步电动机无功补偿容量的配置。结合应用实例说明采用无功补偿技术,提高低压电网和用电设备的功率因数,已成为节电工作的一项重要措施。
  关键词: 节电技术 功率因数 无功补偿
  Abstract: The power factor of equipment can be used to measure the loss of energy in transmission lines. By refining the technique, we can let the power factor which is below the standard get standardized to save electricity. This article analyses the function of reactive compensation and the ways to choose capacity of compensation. It emphasizes in discussing the configuration of low voltage network and asynchronous motor’s capacity in reactive compensation. By combining with actual examples, this article also explains that using the technique of reactive compensation to improve the power factor of low voltage network and equipment has become an important measure to save electricity.
  Key words: Technique of electricity saving ,Power factor, Reactive compensation
  1、前言
  无功补偿,就其概念而言早为人所知,它就是借助于无功补偿设备提供必要的无功功率,以提高系统的功率因数,降低能耗,改善电网电压质量。
  无功补偿的合理配置原则
  从电力网无功功率消耗的基本状况可以看出,各级网络和输配电设备都要消耗一定数量的无功功率,尤以低压配电网所占比重最大。为了最大限度地减少无功功率的传输损耗,提高输配电设备的效率,无功补偿设备的配置,应按照“分级补偿,就地平衡”的原则,合理布局。
  (1)总体平衡与局部平衡相结合,以局部为主。
  (2)电力部门补偿与用户补偿相结合。
  在配电网络中,用户消耗的无功功率约占50%~60%,其余的无功功率消耗在配电网中。因此,为了减少无功功率在网络中的输送,要尽可能地实现就地补偿,就地平衡,所以必须由电力部门和用户共同进行补偿。
  (3)分散补偿与集中补偿相结合,以分散为主。
  集中补偿,是在变电所集中装设较大容量的补偿电容器。分散补偿,指在配电网络中分散的负荷区,如配电线路,配电变压器和用户的用电设备等进行的无功补偿。集中补偿,主要是补偿主变压器本身的无功损耗,以及减少变电所以上输电线路的无功电力,从而降低供电网络的无功损耗。但不能降低配电网络的无功损耗。因为用户需要的无功通过变电所以下的配电线路向负荷端输送。所以为了有效地降低线损,必须做到无功功率在哪里发生,就应在哪里补偿。所以,中、低压配电网应以分散补偿为主。
  (4)降损与调压相结合,以降损为主。
  